| Model SUN-70K-G03 SUN-75K-G03 SUN-80K-G03 SUN-90K-G03 SUN-100K-G03 SUN-110K-G | |||||||||||
| Input Side | |||||||||||
| Max. DC Input Power (kW) | 91 | 97.5 | 104 | 135 | 150 | 150 | |||||
| Max. DC Input Voltage (V) | 1000 | ||||||||||
| Start-up DC Input Voltage (V) 250 | |||||||||||
| MPPT Operating Range (V) | 200-850 | ||||||||||
| Max. DC Input Current (A) | 40+40+40+40 | 40+40+40+40+40+40 | |||||||||
| Max. Short Circuit Current (A) | 60+60+60+60 | 60+60+60+60+60+60 | |||||||||
| No.of MPP Trackers | 4 | 6 | |||||||||
| No.of Strings per MPP Tracker | 4+4+4+4 | 4+4+4+4+4+4 | |||||||||
| Output Side | |||||||||||
| Rated Output Power (kW) | 70 | 75 | 80 | 90 | 100 | 110 | |||||
| Max. Active Power (kW) | 77 | 82.5 | 88 | 99 | 110 | 121 | |||||
| Nominal Output Voltage / Range (V) 3L/N/PE 220/380V, 230/400V | |||||||||||
| Rated Grid Frequency (Hz) | 50 / 60 (Optional) | ||||||||||
| Operating Phase | Three Phase | ||||||||||
| Rated AC Grid Output Current (A) | 106. 1/101.5 | 113.6/108.7 | 121.2/115.9 | 136.4/130.4 | 151.5/144.9 | 166.7/159.4 | |||||
| Rated AC Grid Output Current (A) | 116.7/111.6 | 125/119.6 | 133.3/127.5 | 150/143.5 | 166.7/159.4 | 183.3/175.4 | |||||
| Output Power Factor | 0.8 leading to 0.8 lagging | ||||||||||
| Grid Current THD | <3% | ||||||||||
| DC Injection Current (mA) | <0.5% | ||||||||||
| Grid Frequency Range | 45~55 or 55~65 (Optional)98.8% | ||||||||||
| Efficiency | |||||||||||
| Max. Efficiency | |||||||||||
| Euro Efficiency | 98.3% | ||||||||||
| MPPT Efficiency | >99%Yes | ||||||||||
| Protection | |||||||||||
| DC Reverse-Polarity Protection | |||||||||||
| AC Short Circuit Protection | Yes | ||||||||||
| AC Output Overcurrent Protection | Yes | ||||||||||
| Output Overvoltage Protection | Yes | ||||||||||
| Insulation Resistance Protection | Yes | ||||||||||
| Ground Fault Monitoring | Yes | ||||||||||
| Anti-islanding Protection | Yes | ||||||||||
| Temperature Protection | Yes | ||||||||||
| Integrated DC Switch | Yes | ||||||||||
| Remote Software Upload | Yes | ||||||||||
| Remote Change of Operating Parameters | Yes | ||||||||||
| Surge Protection | DC Type II / AC Type II | ||||||||||
| General Data | |||||||||||
| Cabinet Size (WxHxD mm) | 838×568×326 (Excluding Connectors and Brackets) | ||||||||||
| Weight (kg) | 81 | ||||||||||
| Topology | Transformerless | ||||||||||
| Internal Consumption | <1W (Night) | ||||||||||
| Running Temperature | -25-65℃, >45℃ Derating | ||||||||||
| Ingress Protection | IP65 | ||||||||||
| Noise Emission (Typical) | ≤55 dB | ||||||||||
| Cooling Concept | Smart Cooling | ||||||||||
| Permissible Altitude (m) | 4000 | ||||||||||
| Warranty | 5 Years | ||||||||||
| Grid Connection Standard | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549- 1, G98, G99, C10- 11, UNE217002, NBR16149/NBR16150 | ||||||||||
| Operating Surroundings Humidity | 0- 100% | ||||||||||
| Safety EMC / Standard IEC/EN 61000-6- 1/2/3/4, IEC/EN 62109- 1, IEC/EN 62109-2 | |||||||||||
| Features | |||||||||||
| DC Connection | MC-4 Mateable | ||||||||||
| AC Connection | IP65 Rated Plug | ||||||||||
| Display | LCD 240 × 160 | ||||||||||
| Interface | RS485/RS232/Wifi/LAN | ||||||||||