Model | SUN-5K-SG01HP3-EU-AM2 | SUN-6K-SG01HP3-EU-AM2 | SUN-8K-SG01HP3-EU-AM2 | SUN-10K-SG01HP3-EU-AM2 | SUN-12K-SG01HP3-EU-AM2 | SUN-15K-SG01HP3-EU-AM2 | SUN-20K-SG01HP3-EU-AM2 | SUN-25K-SG01HP3-EU-AM2 | |
Battery Input Data | |||||||||
Battery Type | Lithium-ion | ||||||||
Battery Voltage Range (V) | 160~700 | ||||||||
Max. Charging Current (A) | 37 | 50 | |||||||
Max. Discharging Current (A) | 37 | 50 | |||||||
Number of Battery Input | 1 | ||||||||
Charging Strategy for Li-Ion Battery | Self-adaption to BMS |
PV String Input Data | |||||||||
Max. DC Input Power (W) | 6500 | 7800 | 10400 | 13000 | 15600 | 19500 | 26000 | 32500 | |
Max. DC Input Voltage (V) | 1000 | ||||||||
Start-up Voltage (V) | 180 | ||||||||
MPPT Range (V) | 150-850 | ||||||||
Full Load DC Voltage Range (V) | 195-850 | 195-850 | 260-850 | 325-850 | 340-850 | 420-850 | 500-850 | 625-850 | |
Rated DC Input Voltage (V) | 600 | ||||||||
PV Input Current (A) | 20+20 | 26+20 | 26+26 | ||||||
Max. PV ISC (A) | 30+30 | 39+30 | 39+39 | ||||||
No.of MPP Trackers | 2 | ||||||||
No.of Strings per MPP Tracker | 1+1 | 2+1 | 2+2 |
AC Output Data | ||||||||
Rated AC Output and UPS Power (W) | 5000 | 6000 | 8000 | 10000 | 12000 | 15000 | 20000 | 25000 |
Max. AC Output Power (W) | 5500 | 6600 | 8800 | 11000 | 13200 | 16500 | 22000 | 26000 |
AC Output Rated Current (A) | 7.6/7.3 | 9.1/8.7 | 12.2/11.6 | 15.2/14.5 | 18.2/17.4 | 22.8/21.8 | 30.4/29 | 37.9/36.3 |
Max. AC Output Rated Current (A) | 8.4/8 | 10/9.6 | 13.4/12.8 | 16.7/16 | 20/19.2 | 25/24 | 33.4/31.9 | 39.4/37.7 |
Max. AC Current (A) | 13 | 13 | 18 | 22 | 25 | 30 | 35 | 40 |
Generator input/Smart load /AC couple current (A) | 7.6/40/7.6 | 9.1/40/9.1 | 12.2/40/12.2 | 15.2/40/15.2 | 18.2/80/18.2 | 22.8/80/22.8 | 30.4/80/30.4 | 37.9/80/37.9 |
Max. Continuous AC Passthrough (A) | 40 | 80 | ||||||
Peak Power (offff grid) | 1.5 time of rated power, 10 S | |||||||
Output Frequency and Voltage | 50/60Hz;3L/N/PE 220/380Vac,230/400Vac | |||||||
Power Factor | 0.8 leading to 0.8 lagging | |||||||
Grid Type | Three Phase | |||||||
Total Harmonic Distortion (THD) | <3% (of nominal power) | |||||||
DC current injection | <0.5% In |
Efficiency | |
Max. Efficiency | 97.60% |
Euro Efficiency | 97.00% |
MPPT Efficiency | 99.90% |
Protection | |
Integrated | Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge Protection |
Output Over Voltage Protection | DC Type II / AC Type Ⅲ |
Certifications and Standards | |
Grid Regulation | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 |
Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
General Data | |
Operating Temperature Range (℃) | -40~60℃, >45℃ Derating |
Cooling | Smart cooling |
Noise (dB) | ≤55 dB |
Communication with BMS | RS485; CAN |
Weight (kg) | 30.5 |
Cabinet Size (WxHxD mm) | 408×638×237 (Excluding Connectors and Brackets) |
Protection Degree | IP65 |
Installation Style | Wall-mounted |
Warranty | 5 Years (10 Years Optional) |